NC100LE 1P+N
Suitable for the circuit of 50Hz, rated voltage 230/400V, and rated current up to 100A. It has the earth leakage,overload&short circuit protect function.
Email: xjq2979@gmail.com
Contact person: Mr Xiao (International Dept)
Tel:+86-13480220198 +86-20-87089666
Fax:+86-20-87089666
Address:Xianliedong Road,Tianhe, Guangzhou 510000, China
Suitable for the circuit of 50Hz, rated voltage 230/400V, and rated current up to 100A. It has the earth leakage,overload&short circuit protect function.
Application:
NC100LE RCBO is suitable for the circuit of 50Hz, rated voltage 230/400V, and rated current up to 100A. It has the earth leakage,overload&short circuit protect function. It can aslo add over voltage protect function. It is mainly used in building illumination and electrical distribution system.
Specifications:
Number of Poles | 1P+N,2P,3P,3P+N,4P |
Rated Current(A) | 40,50,63,80,100 |
Rated Residual Operating Current(I△n)(mA) | 30,50,100,200,300 |
Rated Residual Non-operation Current(I△no)(mA) | ≤0.5I△n |
Rated Voltage(V) | AC230/400 |
Residual Current Off-time | ≤0.1S |
Short Circuit Capacity(Icu) | 3000A |
Endurance | ≥4000 |
Tipping Curve | C,D |
Protection Degree | IP20 |